TYPE 95DSS3
Integrated Flame Scanner
II
SIL3
DESCRIPTION
The Fireye 95DSS3 InSight II is a family of versatile fully microprocessor based, integrated flame
scanners. The 95DSS3 holds multiple worldwide safety agency approvals (see Model Listings for
full details).
The InSight II scanners utilize advanced techniques for discrimination and integrate the flame detec-
tion, amplification, safety determination and flame switch functions into a single detection head. No
separate amplifier or flame switch module is therefore required to interface with the main burner
management system.
InSight II incorporates the superior detection and discrimination elements of the popular InSight
product with additional enhanced capability, features and benefits.
The scanner measures the amplitude of the modulations (the flame “flicker”) that occur within the
targeted flame. During the scanner set-up procedure, the modulation frequency that yields the best
flame ON/OFF discrimination is selected. The appropriate modulation frequency and sensor gain
can be either manually or automatically selected.
InSight II is a dual cell scanner utilizing UV and IR detector and various levels of housing type
including FM Class I Div 2 and ATEX ExdIIC (see Model Listing for full description of options).
Standard features include two independently adjustable Flame Relays that can be selected to operate
from the UV sensor, the IR sensor, or both sensors, 21 choices of modulation frequency, adjustable
sensor gain, adjustable flame relay ON/OFF thresholds, two 4-20 mA analog signal strength outputs
(one for FR1 and one for FR2), Fault Relay, four selectable programmable files (e.g. for different
fuels or firing rates), and Auto Config capability with manual override. Remote communication
capability is available via optional “Fireye Explorer” PC software (CU-109).
Ordered separately, a blank cover, or two different operator interfaces are available for the standard
(non-CEX) InSight II scanners enabling the user to view and change the operating parameters and
setpoints.
Model 95DISP-1 and 95DISP-1-SS are two-line by sixteen-character alpha-numeric VFD Displays
with five-pushbutton keypads. The 95DISP-1 is installed by the user onto the end of the scanners.
The 95DISP-1-SS is factory installed into the 95DSS3-1CEXSS and 95DSS3-1CEX-2 scanners.
Model 95WIDISP-2 is an Infrared Transmitter, installed by the user onto the end of the scanner
instead of a display. The 95WIDISP-2 transmitter provides wireless communications to a model
95WIHH-2 hand-held remote communications tool.
CU-113
OCTOBER 8, 2014
Zobrazit stránku 0
1 2 3 4 5 6 ... 61 62

Shrnutí obsahu

Strany 1 - Integrated Flame Scanner

1TYPE 95DSS3Integrated Flame ScannerIISIL3DESCRIPTIONThe Fireye 95DSS3 InSight II is a family of versatile fully microprocessor based, integrated fl

Strany 2 - Safety Information

10Operator Interface: P/N 95DISP-1, 95DISP-1-SS, Alpha -Numeric Display with five pushbutton keys.P/N 95WIDISP-2 Infrared Transmitter, used in conjun

Strany 3 - TABLE OF CONTENTS

11FIGURE 4. SINGLE BURNER SCANNER SIGHTING4. Consideration must be given to burner secondary air rotation, some burners have clockwise(CW) air rotat

Strany 4 - APPLICATION

127. In larger multi-burner type applications such as power, kiln or refinery burners, it is recognizedthat there may be several obstructions within

Strany 5 - DIMENSIONS

13Orifice Kit (Optional)An orifice may be used to restrict the scanner’s field of view aiding discrimination between the tar-get flame and other fla

Strany 6 - FINISH:

14FIGURE 7.FIGURE 8.FIGURE 9.PART NUMBERA. SWIVEL MOUNT 60-1664-3 (NPT)60-1664-4 (BSP)B. 1" WYE 35-200 (NPT)C. 1” CLOSE NIPPLE 35-201 (NPT)D. S

Strany 7 - 60-2693-4 (BSP)

15FIGURE 10.FIGURE 11.ORIFICESFigure Qty. Part Number Description11 1 53-121 Orifice Kit: Contains following items:11A 1 53-121-2 Orifice: Diameter

Strany 8 - MODEL LISTING

16FIGURE 12.ELECTRICAL ACCESSORIES (see note)Note: Hazardous Area requirements for InSight II scanners with electrical connectors:1. For hazardous lo

Strany 9 - SPECIFICATIONS

17Scanner Cable with Female Connector, P/N 59-546-x, 59-547-xFireye offers the 59-546 (8-conductor) and 59-547 (12-conductor) cables in precut lengt

Strany 10 - INSTALLATION PROCEDURE

18SCANNER DISPLAYS (for standard / non-CEX models)Scanner Display, P/N 95DISP-1, 95DISP-1-SSP/N 95DISP-1 is a two-line by sixteen-character alpha-num

Strany 11 - Obstruction

19FIGURE 13. WIRING DIAGRAM, MODEL 95DSS3-1 INSIGHT II FLAME SCANNERNotes: (see page 21)FLAMERELAY 1(Note 1)FLAMERELAY 2(Note 1)FAULTRELAY(Note 2,3)

Strany 12 - MECHANICAL ACCESSORIES

2Model 61-7347-1 is a Blank Cover installed by the user onto the end of the scanner to maintain envi-ronmental ratings when neither the 95DISP-1 nor

Strany 13

20FIGURE 14. RETROFIT WIRING DIAGRAM, MODEL 95DSS3-1WINC INSIGHT II SCANNER USING INSIGHT I CABLE Notes: (see page 21)FLAMERELAY 1(Note 1)FLAMERELAY

Strany 14 - FIGURE 8

21Notes:FIGURE 15. INSIGHT II CABLE CONNECTOR, Female Pin OrientationQUICK DISCONNECT PINS1. Flame relay contacts are shown in de-energized (no flam

Strany 15 - ORIFICES

22FIGURE 16. WIRING FOR 95DSS3-1WOC, 95DSS3-1CEX, 95DSS3-1WICEX SCANNERS8-PIN TERMINAL BLOCK 9-PIN TERMINAL BLOCK59-546 Cable Color (if used)Pin Num

Strany 16

23FIGURE 17. WIRING FOR 95DSS3-1CEXSS and 95DSS3-1CEX-2 scanners (shown with housing cover removed))8-PIN TERMINAL BLOCK 9-PIN TERMINAL BLOCKREMOTE

Strany 17

24WIRING FOR REMOTE COMMUNICATIONS Remote communications with the InSight II scanner uses an RS485 Interface to carry the communi-cation signals. A W

Strany 18 - SCANNER WIRING

25FIGURE 19. INSIGHT I to INSIGHT II CONVERSION HARNESS (using existing InSight I cable)FIGURE 20. WIRING DIAGRAM FOR P/N 59-4647-10TB CONVERSION HA

Strany 19 - Type 95DSS3-1

26GROUNDING AND SHIELDING TECHNIQUESFOR USE ON SCANNERS OR SCANNER CABLE LOCATED WITHIN 12" OF A HIGHENERGY OR HIGH VOLTAGE SOURCE.1. Connect a

Strany 20 - Type 95DSS3-1WINC

27INSIGHT II MENU STRUCTUREFor ease of operation, the InSight II scanner contains five primary menus (or loops) accessed via thekeypad and viewed on

Strany 21 - QUICK DISCONNECT PINS

28FIGURE 21. INSIGHT II SCANNER MENU STRUCTUREMAINSTATUSMENUFig 22, Pg 29PASSWORDMENUFig 24, Pg 36MANUALCONFIGFR2Pg 53MANUALCONFIG FR1Pg 53CONFIGMENU

Strany 22 - 9-PIN TERMINAL BLOCK

29THE MAIN STATUS MENUFIGURE 22. MAIN STATUS MENU LOOPTo Password Menu1=OFF 2=OFF F=AFQ 1:000 2:000Fri Jan 01, 2010FS:KEY 23:14:36MAX. TEMP XXXCCU

Strany 23 - REMOTE FILE SELECTION

3TABLE OF CONTENTSDESCRIPTION...1OPERATION...4APPLICATION...

Strany 24 - MANAGEMENT

30THE MAIN STATUS MENUNote: HELP text information for many main menu functions is displayed when you press the Fireyelogo. The text will appear in th

Strany 25

31Current Temp(CUR TEMP) This displays the current internal temperature of the scanner unit. This value togglesbetween degrees Fahrenheit and Celsiu

Strany 26

32Learn StatusStatus values can be MAN, ON, OFF, or BOTH. (see note)MAN: Manual mode, no Learning done, or USER has changed at least ONEof the lear

Strany 27 - INSIGHT II MENU STRUCTURE

33Select To Enter Error HistoryPress Select Key to enter the Error History screen to view error status and codes. The most recentError is displayed

Strany 28

34Internal Error MessagesSelect To Enter Configure MenuPressing the Select Key will bring you to the Password Entry Screen before accessing the Confi

Strany 29 - THE MAIN STATUS MENU

35Group II Warning Messages (Can be suppressed, see Note 1)Notes1. Group II Warning messages are suppressed whenever “Do NOT Display” is selected un

Strany 30

36THE PASSWORD MENUFIGURE 24. PASSWORD MENU LOOPPSELECT KeyUP Key (Scrolls through menu, counter clockwise)DOWN Key (Scrolls through menu, clockwise)

Strany 31

37THE PASSWORD MENUPasswordA four-digit Password is required to enter the CONFIG menus. If a Password is not entered, pressingthe SELECT key will ad

Strany 32

38THE CONFIG MENUFIGURE 25. CONFIG MENU LOOPPSELECT KeyPROGRAM KeyUP Key (Scrolls through menu, counter clockwise)DOWN Key (Scrolls through menu, clo

Strany 33 - THE ERROR HISTORY MENU

39THE CONFIG MENU (continued)FIGURE 26. CONFIG MENU LOOPPSELECT KeyUP Key (Scrolls through menu, counter clockwise)DOWN Key (Scrolls through menu, c

Strany 34

4OPERATIONThe InSight II has numerous adjustment options available. It can be tuned either automatically ormanually to achieve the optimum level of s

Strany 35

40THE CONFIG MENUTo select a specific item to change from the Config Menu, scroll to it using the UP and DOWNarrows, then press the SELECT button. (T

Strany 36 - THE PASSWORD MENU

41SELECT to Enter AUTOMATIC CONFIGPress the SELECT key to enter Automatic Configuration menu. This option will walk you throughthe configuration pro

Strany 37

42THE AUTO CONFIG MENUFIGURE 27. AUTO CONFIG MENU LOOPAIM SCANNERIR=00 UV=00START LEARN >FR1 and FR2 ON >START LEARN >FR1 a

Strany 38 - THE CONFIG MENU

43THE AUTO CONFIG MENUAuto Configuration is an automatic calibration function whereby the InSight II scanner scans theflame flicker frequency spectr

Strany 39 - THE CONFIG MENU (continued)

44START LEARN FR1 and FR2 ONTo begin LEARN Flame ON for Both FR1 & FR2, make sure flame is at LOW Fire position andpress the PROGRAM key. A promp

Strany 40

45THE FILE COPY MENUFIGURE 28. FILE COPY MENU LOOPPSELECT KeyUP Key (Scrolls through menu, counter clockwise)DOWN Key (Scrolls through menu, clockwi

Strany 41

46THE FILE COPY MENUCopy FROM FileThe source file to Copy from. Valid files are 3 factory configured files (F1, F2, F3) and user configu-rable files

Strany 42 - THE AUTO CONFIG MENU

47THE 4/20 mA MENUFIGURE 29. 4/20mA MENU LOOPPSELECT KeyUP Key (Scrolls through menu, counter clockwise)DOWN Key (Scrolls through menu, clockwise)FR

Strany 43

48THE 4/20 mA MENUFR1 4/20 SELECTThe user may select which parameter the 4-20 mA analog output represents for FR1. Choices areFlame QUALITY or Flame

Strany 44

49THE DATE/TIME MENUFIGURE 30. DATE/TIME MENU LOOPPSELECT KeyUP Key (Scrolls through menu, counter clockwise)DOWN Key (Scrolls through menu, clockwi

Strany 45 - Status Menu

5InSight II SCANNER FEATURESDIMENSIONSFIGURE 1. SCANNER TYPE 95DSS3-1, 95DSS3-1WOC, 95DSS3-1WINCFeatures Basic Models Flame-Proof Hazardous Area Mo

Strany 46 - THE FILE COPY MENU

50THE DATE/TIME MENUThe InSight II scanner has a real time clock for date/time stamping error information. The user mustset the clock to the current

Strany 47 - THE 4/20 mA MENU

51THE COMMS MENUFIGURE 31. COMMS MENU LOOPPSELECT KeyUP Key (Scrolls through menu, counter clockwise)DOWN Key (Scrolls through menu, clockwise)MODBU

Strany 48

52THE COMMS MENUMODBUS ADDRESSThis option allows the user to select the device modbus address. (Affects all files)The communications address selected

Strany 49 - THE DATE/TIME MENU

53THE MANUAL CONFIG MENUSFIGURE 32. MANUAL CONFIG MENU LOOP for FR1 (FR2 is similar)PSELECT KeyUP Key (Scrolls through menu, counter clockwise)DOWN

Strany 50

54THE MANUAL CONFIG MENUSThere are two MANUAL CONFIG menus, one for each flame relay, FR1 and FR2.In each MANUAL CONFIG menu, the user may select the

Strany 51 - THE COMMS MENU

55SELECT to Exit BACK to MAINReturns to Main Status MenuTHE IR and UV SETTINGS MENUSFIGURE 33. IR SETTINGS MENU LOOP (UV is similar)R1AIR-BAND(Freq)

Strany 52

56THE IR AND UV SETTINGS MENUSEach MANUAL CONFIG menu contains two sub-menus, IR SETTINGS and UV SETTINGS. Inthe IR and UV SETTINGS menus, the user m

Strany 53 - THE MANUAL CONFIG MENUS

57It may be necessary to adjust the sensor GAIN in order to keep the signal strength value on scale. Ifso, observe and record the sensor GAIN value

Strany 54

58INSIGHT II FACTORY DEFAULT SETTINGS, USER FILES A,B,C,D and Factory File F3PARAMETER DEFAULT VALUE ALLOWABLE VALUESConfig Menu:Remote File SelKey P

Strany 55 - PROGRAM Key

59Factory Files F1, F2, F3:F1 (High Sensitivity): The IR and UV BAND settings are 23 Hz. The IR and UV USER GAIN settings are 31. The IR and UV FEG

Strany 56 - THE IR AND UV SETTINGS MENUS

6FIGURE 2. TYPE 95DSS3-1CEX, -1WICEX, -1CEX-ND SCANNERS, STANDARD FLAME-PROOF HAZARDOUS AREA HOUSING • Window joints are cemented using Aremco bond 5

Strany 57

60INSIGHT II CONFIGURATION RECORD - continued -Parameter FILE A FILE B FILE C FILE DConfig Menu:Remote File SelPASSWORDFS Squelch MsgsIR GAIN RANGEUV

Strany 58

61INSIGHT II CONFIGURATION RECORD (continued)INSIGHT II REPLACEMENT PROCEDUREThis procedure may be followed when replacing a damaged InSight II scan

Strany 59

62ORDERING INFORMATIONExample: To select the Fireye equipment meeting the following specification:InSight II scanner, dual sensor, surface mounted NE

Strany 60 - - continued

7FIGURE 3. TYPE 95DSS3-1CEXSS, -1CEX-2, SCANNERS, OPTIONAL FLAME-PROOF HAZARDOUS AREA HOUSINGSNote: Model 95DSS3-1CEX includes the 95DISP-1 Display.

Strany 61

8MODEL LISTINGNotes: 1. Hazardous area ratings (Class I, Class II and ATEX) certified by FM unless otherwise noted.2. Hazardous area requirements for

Strany 62 - WARRANTIES

96. UL Functional Safety Listed Primary Safety Control 5AC0 EN/IEC 61508, Parts 1-7 (2010) up to SIL3. ANSI/UL 1998 (2008) Class 2* For use with wir